1 i/o wiring examples – FanAm MD60 AC Drive User Manual

Page 37

Advertising
background image

Installing Control Wiring

6-5

6.4.1 I/O Wiring Examples

Input/Output

Connection Example

Potentiometer
1-10k Ohm Pot.
Recommended
(2 watt minimum)

P038 (Speed Reference) = 2 “0-10V Input”

Analog Input
0 to +10V, 100k ohm
impedance
4-20 mA, 100 ohm
impedance

Voltage

P038 (Speed Reference) = 2

“0-10V Input”

Current

P038 (Speed Reference) = 3

“4-20mA Input”

2 Wire SRC Control
Non-Reversing
P036 (Start Source) = 2, 3 or
4
Input must be active for the
drive to run. When input is
opened, the drive will stop as
specified by P037 (Stop
Mode).
If desired, a User Supplied
24 V DC power source can
be used. Refer to the
“External Supply (SRC)”
example.

Internal Supply (SRC)

External Supply (SRC)

2 Wire SNK Control Non-
Reversing

Internal Supply (SNK)

Figure 6.2 – I/O Wiring Examples

12

13

14

13

14

+

Common

14

15

Common

+

11

01

02

Stop-Run

+24V

Common

01

02

04

Stop-Run

01

02

04

Stop-Run

Advertising