Basic Program Group Parameters

The Basic Program Group contains the most commonly used
parameters to simplify the start-up process.

Set to the motor nameplate rated volts.

Set to the motor nameplate rated frequency.

Set to the maximum allowable motor current. The drive will fault on
an F7 Motor Overload if the value of this parameter is exceeded by
150% for 60 seconds or 200% for 3 seconds.

Sets the lowest frequency the drive will output continuously.

Sets the highest frequency the drive will output.

P031 Motor NP Volts

Range:

20 VAC to Drive Rated Volts

Default:

Based on Drive Rating

See also:

A084

P032 Motor NP Hertz

Range:

10 to 240 Hz

Default:

60 Hz

See also:

A084

P033 Motor OL Current

Range:

0.0 to (Drive Rated Amps x 2)

Default:

Based on Drive Rating

See also:

A089, A090, A098

P034 Minimum Frequency

Range:

0.0 to 240.0 Hz

Default:

0.0 Hz

See also:

d001, d002, d013, P035, A110, A112, A115

P035

Maximum Frequency

Range:

0 to 240 Hz

Default:

60 Hz

See also:

d001, d002, d013, P034, A078, A111, A113, A115