Troubleshooting the Drive

10-5

F48

Params
Defaulted

N The drive was

commanded to write
default values to
EEPROM.

Clear the fault or cycle
power to the drive.

Program the drive
parameters as needed.

F63

SW
OverCurrent

Y Programmed A098

(SW Current Trip) has
been exceeded.

Check load requirements
and A098 (SW Current
Trip) setting.

F64

Drive
Overload

N Drive rating of 150%

for 1 minute has been
exceeded.

Reduce load or extend
Accel Time.

F70

Power Unit

N Failure has been

detected in the drive
power section.

Cycle power.

Replace drive if fault
cannot be cleared.

F81

Comm Loss

N RS485 port stopped

communicating.

If module was not
intentionally
disconnected, check
wiring to the port.
Replace wiring, port
expander, module or
complete drive as
required.

Check connection.

A module was
intentionally
disconnected.

Turn off using A105
(Comm Loss Action).

F100 Parameter

Checksum

N The checksum read

from the board does
not match the
checksum calculated.

Set P041 (Reset to
Defaults) to option 1
(Reset Defaults).

F122 I/O Board Fail N Failure has been

detected in the drive
control and I/O section.

Cycle power.

Replace drive if fault
cannot be cleared.

1

Refer to section 10.1.2 for information about the Auto Restart Feature.

Table 10.1 – Fault Descriptions and Corrective Actions (Continued)

No.

Fault

A

u

to-Reset

1

?

Description

Action