10-4

MD60 AC Drive User Manual

F8

Heatsink
OverTemp

Y Heatsink temperature

exceeds a predefined
value.

Check for blocked or
dirty heat sink fins.
Verify that ambient
temperature has not
exceeded 40

°

C (104

°

F)

for IP 30/NEMA 1/UL
Type 1 installations or 50°C
(122°F) for Open type
installations.

Check fan.

F12

HW
OverCurrent

N The drive output

current has exceeded
the hardware current
limit.

Check programming.
Check for excess load,
improper Start Boost
(A084) setting, DC brake
volts set too high, or other
causes of excess current.

F13

Ground Fault

N A current path to earth

ground has been
detected at one or
more of the drive
output terminals.

Check the motor and
external wiring to the drive
output terminals for a
grounded condition.

F33

Auto Restart
Tries

N Drive unsuccessfully

attempted to reset a
fault and resume
running for the
programmed number
of Auto Restart Tries in
A092.

Correct the cause of the
fault and manually clear.

F38

Phase U to
Gnd

N A phase to ground fault

has been detected
between the drive and
motor in this phase.

Check the wiring
between the drive and
motor.

Check motor for
grounded phase.

Replace drive if fault
cannot be cleared.

F39

Phase V to
Gnd

F40

Phase W to
Gnd

F41

Phase UV
Short

N Excessive current has

been detected
between these two
output terminals.

Check the motor and
drive output terminal
wiring for a shorted
condition.

Replace drive if fault
cannot be cleared.

F42

Phase UW
Short

F43

Phase VW
Short

Table 10.1 – Fault Descriptions and Corrective Actions (Continued)

No.

Fault

A

u

to-Reset

1

?

Description

Action