Sets the time between restart attempts when Auto Restart Tries
(A092) is set to a value other than zero. Refer to section 10.1.2 for
more information on the Auto Restart/Run feature.

Enables/disables a feature that allows a Start or Run command to
automatically cause the drive to resume running at commanded
speed after drive input power is restored. Requires a digital input
configured for Run or Start and a valid start contact.

This parameter will not function if parameter P036 (Start Source) is
set to option 1 (3-Wire) or option 4 (2-Wire High Speed).

Enables/disables the function that allows the direction of motor
rotation to be changed. The reverse command may come from a
digital command, the keypad, or a serial command. All reverse
inputs including two-wire Run Reverse will be ignored with reverse
disabled.

A093 Auto Restart Delay

Range:

0.0 to 120.0 sec

Default:

1.0 sec

See also:

A092

A094 Start At Power Up

Range:

0 = Disabled
1 = Enabled

Default:

0 = Disabled

See also:

N/A

!

ATTENTION: Equipment damage and/or personal
injury may result if this parameter is used in an
inappropriate application. Do not use this function
without considering applicable local, national, and
international codes, standards, regulations, or
industry guidelines.

A095 Reverse Disable

Range:

0 = Reverse Enabled
1 = Reverse Disabled

Default:

0 = Reverse Enabled