Input/Output Rating

Output Frequency:

0-240 Hz (Programmable)

Efficiency:

97.5% (Typical)

Digital Control Inputs (Inputs Current = 6 mA)

SRC (Source)
Mode:

18-24 V = ON
0-6 V = OFF

SNK (Sink) Mode:

0-6 V = ON
18-24 V = OFF

Analog Control Inputs

4-20 mA Analog:

250 ohm input impedance

0-10 V DC Analog:

100k ohm input impedance

External Pot:

1-10 k ohms, 2 Watt minimum

Control Output

Programmable Output (form C relay)

Resistive Rating:

3.0 A at 30 V DC, 3.0 A at 125 V AC, 3.0 A at
240 V AC

Inductive Rating:

0.5 A at 30 V DC, 0.5 A at 125 V AC, 0.5 A at
240 V AC

Fuses and Circuit Breakers

Recommended
Fuse Type:

UL Class J, CC, T or Type BS88; 600 V (550 V) or
equivalent.

Recommended
Circuit Breakers:

HMCP circuit breakers or equivalent.

Protective Features

Motor Protection:

I

2

t overload protection - 150% for 60 sec, 200% for

3 sec (Provides Class 10 protection)

Overcurrent: 200%

hardware

limit, 300% instantaneous fault

Over Voltage:

• 100-120 V AC Input – Trip occurs at 405 V DC bus

voltage (equivalent to 150 V AC incoming line

• 200-240 V AC Input – Trip occurs at 405 V DC bus

voltage (equivalent to 290 V AC incoming line)

• 380-460 V AC Input – Trip occurs at 810 V DC bus

voltage (equivalent to 575 V AC incoming line)

Advertising