FanAm MD60 AC Drive User Manual

Page 73

Advertising
background image

Parameter Descriptions

9-23

0 = Fault (Default): Drive will fault on an F81 Comm Loss and coast
to stop.

1 = Coast to Stop: Stops the drive via coast to stop.

2 = Stop: Stops the drive via the setting in Stop Mode (P037).

3 = Continue Last Speed: Drive continues operating at
communication commanded speed saved in RAM.

Sets the time that the drive will remain in communication loss before
implementing the option selected in Comm Loss Action (A105).

Determines details related to the specific RS485 protocol used by
the drive.

Important:

Cycle power after changing this parameter for the
value to take effect.

A106 Comm Loss Time

Range:

0.1 to 60.0

Default:

5.0

See also:

d015, A105

A107 Comm Format

Range:

0 = RTU 8-N-1 3 = RTU 8-N-2
1 = RTU 8-E-1 4 = RTU 8-E-2
2 = RTU 8-O-1 5 = RTU 8-O-2

Default:

0 = RTU 8-N-1

See also:

N/A

Advertising