9-18

MD60 AC Drive User Manual

.

Sets the carrier frequency for the PWM output waveform. Figure 9.9
provides derating guidelines based on the PWM frequency setting.

Important:

Ignoring derating guidelines can cause reduced drive
performance.

Sets the maximum number of times the drive attempts to reset a
fault and restart. Refer to section 10.1.2 for more information on the
Auto Restart/Run feature.

A091 PWM Frequency

Range:

2.0 to 16.0 kHz

Default:

4.0 kHz

See also:

N/A

Figure 9.9 – Derating Guidelines Based on PWM Frequency (A091)

Selection

68

84

88

80
76

96

100

92

72

64
60
56
52

8

7

6

5

4

3

2

1

15

14

16

13

12

11

10

9

A092 Auto Restart Tries

Range:

0 to 9

Default:

0

See also:

A093

!

ATTENTION: Equipment damage and/or personal
injury may result if this parameter is used in an
inappropriate application. Do not use this function
without considering applicable local, national, and
international codes, standards, regulations, or
industry guidelines.