2 advanced group parameters – FanAm MD60 AC Drive User Manual

Page 58

Advertising
background image

9-8

MD60 AC Drive User Manual

9.2

Advanced Group Parameters

Selects the function for the digital inputs. Refer to the flowchart in
section 6.6 for more information on speed reference control priority.

0 = Not Used.

1 = Accel Time 2 (A067) and Decel Time 2 (A068): When this
option is selected, Accel Time 2 and Decel Time 2 are used for all
ramp rates except Jog. Refer to the flowchart in section 6.7 for more
information about accel/decel selection.

2 = Jog: When input is present, the drive accelerates according to
the value set in Jog Accel/Decel (A079) and ramps to the value set
in Jog Frequency (A078). When the input is removed, the drive
ramps to a stop according to the value set in Jog Accel/Decel. A
valid Start command will override this input.

3 = Auxiliary Fault: When enabled, an F2 Auxiliary Input fault will
occur when the input is removed.

4 = Preset Frequencies (Default) See Preset Frequency x (A070
to A073).

Important:

Digital Input 1 or 2 has priority for frequency control
when it is programmed as a Preset Speed and is
active.

5 = Local: When active, sets the integral keypad as the start source
and the potentiometer on the integral keypad as the speed source.

A051
A052

Digital In1 Select (I/O Terminal 05)
Digital In2 Select (I/O Terminal 06)

Range:

0 = Not Used
1 = Accel 2 & Decel 2

1

2 = Jog
3 = Auxiliary Fault
4 = Preset Frequencies
5 = Local
6 = RS485 Port

1

7 = Clear Fault
8 = Ramp Stop, CF
9 = Coast Stop, CF
10 = DCIj Stop, CF
11 = Jog Forward
12 = Jog Reverse
13 = 10V In Ctrl
14 = 20mA In Ctrl
26 = Anlg Invert

1

Can be tied to only one input.

Default:

4 = Preset Frequencies

See also:

A067, A068, A070 through A073, A078, A079