FanAm MD60 AC Drive User Manual

Page 85

Advertising
background image

Troubleshooting the Drive

10-3

Use caution when enabling this feature since the drive will attempt
to issue its own start command based on user-selected
programming.

Table 10.1 – Fault Descriptions and Corrective Actions

No.

Fault

A

u

to-Reset

1

?

Description

Action

F2

Auxiliary
Input

Y Auxiliary input interlock

is open.

Check remote wiring.

Verify communications
programming for
intentional fault.

F3

Power Loss

N DC bus voltage

remained below 85%
of nominal.

Monitor the incoming
AC line for low voltage
or line power
interruption.

Check input fuses.

F4

UnderVoltage Y DC bus voltage fell

below the minimum
value.

Monitor the incoming AC
line for low voltage or line
power interruption.

F5

OverVoltage

Y DC bus voltage

exceeded maximum
value.

Monitor the AC line for
high line voltage or
transient conditions. Bus
overvoltage can also be
caused by motor
regeneration. Extend the
decel time or install
dynamic brake option.

F6

Motor Stalled Y Drive is unable to

accelerate motor.

Increase Accel Time x
(P039, A067) or reduce
load so drive output
current does not exceed
the current set by
parameter A089 (Current
Limit).

F7

Motor
Overload

Y Internal electronic

overload trip.

An excessive motor load
exists. Reduce load so
drive output current
does not exceed the
current set by parameter
P033 (Motor OL
Current).

Verify Start Boost
(A084) setting.

Advertising