4 wiring the control terminal block – FanAm MD60 AC Drive User Manual

Page 36

Advertising
background image

6-4

MD60 AC Drive User Manual

6.4

Wiring the Control Terminal Block

No.

Signal

Default

Description

Parameter

R1

Relay N.O.

Fault

Normally open contact for output relay.

A055

R2

Relay Common

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

A055

Sink/Source DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.

01

Stop

(1)

Coast

The factory-installed jumper or a normally closed input
must be present for the drive to start.

P036

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default. To
disable reverse operation, see A095 (Reverse Disable).

P036, P037

03

Dir/Run REV

Not Active

P036, P037, A095

04

Digital Common

For digital inputs. Electronically isolated with digital
inputs from analog I/O.

05

Digital Input 1

Preset 1

Program with A051 (Digital In1 Select).

A051

06

Digital Input 2

Preset 2

Program with A052 (Digital In2 Select).

A052

11

+24V DC

Drive supplied power for digital inputs.

12

+10V DC

Drive supplied power for 0-10V external potentiometer.

P038

13

0-10V In

(3)

Not Active

For external 0-10V input supply
(input impedance = 100k ohm) or potentiometer wiper.

P038

14

Analog Common

For 0-10V In or 4-20mA In. Analog inputs electrically
isolated from digital I/O.

15

4-20mA In

(3)

Not Active

For external 4-20mA input supply
(input impedance = 250 ohm).

P038

16

RS485 Shield

Terminal should be connected to chassis ground when
using the RS485 communications port.

(3)

Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time,

an undetermined frequency reference will result.

(

4) RS485 port is used to connect the drive to a personal computer running VS Utilities via a Serial Converter module, and for

connection to the Remote Nema 4x/12 or Copy Cat Keypads.

Figure 6.1 – Wiring the Control Terminal Block

30V DC 125V AC 230V AC

Resistive

3.0A

3.0A

3.0A

Inductive

0.5A

0.5A

0.5A

(1)

Important: I/O Terminal 01

is always a coast-to-stop input
except when P036 (Start Source)
is set to 3-Wire Control. In three-
wire control, I/O Terminal 01 is
controlled by P037 (Stop
Mode).
All other sources are
controlled by
P037 (Stop Mode).

Important: The drive is
shipped with a jumper
installed between I/O
Terminals 01 and 11.
Remove this jumper when
using I/O Terminal 01 as a
stop or enable input.

(2)

Two-wire control shown.

For three-wire control, use a
momentary input

on

I/O Terminal 02 to command
a start. Use a maintained
input

for I/O Terminal

03 to change direction.

P036 (Start Source)

Stop

I/O Terminal 01 Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

2-Wire

Per P037

Coast

RS485

Per P037

Coast

01

02

03

04

05

06

11

12

13

14

15

16

Stop

(1)

Start/Run FWD

(2)

Direction/Run REV

Digital Common

Digital Input 1

Digital Input 2

R1

R2

R3

Relay N.O.

Relay Common

Relay N.C.

+24V DC

+10V DC

0-10V In

Analog Common

4-20mA In

RS485 Shield

+24V

+10V

SRC

SNK

Typical

SNK Wiring

Typical

SRC Wiring

1

8

RS485

(DSI)

R1 R2 R3

01

02

03

04

05

06

11

12

13

14

15

16

SNK

SRC