4 wiring the control terminal block – FanAm MD60 AC Drive User Manual

Page 36

Advertising
background image

6-4

MD60 AC Drive User Manual

6.4

Wiring the Control Terminal Block

No.

Signal

Default

Description

Parameter

R1

Relay N.O.

Fault

Normally open contact for output relay.

A055

R2

Relay Common

–

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

A055

Sink/Source DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.

01

Stop

(1)

Coast

The factory-installed jumper or a normally closed input
must be present for the drive to start.

P036

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default. To
disable reverse operation, see A095 (Reverse Disable).

P036, P037

03

Dir/Run REV

Not Active

P036, P037, A095

04

Digital Common

–

For digital inputs. Electronically isolated with digital
inputs from analog I/O.

05

Digital Input 1

Preset 1

Program with A051 (Digital In1 Select).

A051

06

Digital Input 2

Preset 2

Program with A052 (Digital In2 Select).

A052

11

+24V DC

–

Drive supplied power for digital inputs.

12

+10V DC

–

Drive supplied power for 0-10V external potentiometer.

P038

13

0-10V In

(3)

Not Active

For external 0-10V input supply
(input impedance = 100k ohm) or potentiometer wiper.

P038

14

Analog Common

–

For 0-10V In or 4-20mA In. Analog inputs electrically
isolated from digital I/O.

15

4-20mA In

(3)

Not Active

For external 4-20mA input supply
(input impedance = 250 ohm).

P038

16

RS485 Shield

–

Terminal should be connected to chassis ground when
using the RS485 communications port.

(3)

Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time,

an undetermined frequency reference will result.

(

4) RS485 port is used to connect the drive to a personal computer running VS Utilities via a Serial Converter module, and for

connection to the Remote Nema 4x/12 or Copy Cat Keypads.

Figure 6.1 – Wiring the Control Terminal Block

30V DC 125V AC 230V AC

Resistive

3.0A

3.0A

3.0A

Inductive

0.5A

0.5A

0.5A

(1)

Important: I/O Terminal 01

is always a coast-to-stop input
except when P036 (Start Source)
is set to 3-Wire Control. In three-
wire control, I/O Terminal 01 is
controlled by P037 (Stop
Mode).
All other sources are
controlled by
P037 (Stop Mode).

Important: The drive is
shipped with a jumper
installed between I/O
Terminals 01 and 11.
Remove this jumper when
using I/O Terminal 01 as a
stop or enable input.

(2)

Two-wire control shown.

For three-wire control, use a
momentary input

on

I/O Terminal 02 to command
a start. Use a maintained
input

for I/O Terminal

03 to change direction.

P036 (Start Source)

Stop

I/O Terminal 01 Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

2-Wire

Per P037

Coast

RS485

Per P037

Coast

01

02

03

04

05

06

11

12

13

14

15

16

Stop

(1)

Start/Run FWD

(2)

Direction/Run REV

Digital Common

Digital Input 1

Digital Input 2

R1

R2

R3

Relay N.O.

Relay Common

Relay N.C.

+24V DC

+10V DC

0-10V In

Analog Common

4-20mA In

RS485 Shield

+24V

+10V

SRC

SNK

Typical

SNK Wiring

Typical

SRC Wiring

1

8

RS485

(DSI)

R1 R2 R3

01

02

03

04

05

06

11

12

13

14

15

16

SNK

SRC

(1)