10.2 Troubleshooting Tables

Use the following tables to troubleshoot the drive. If you cannot
resolve the problem using these tables, contact Reliance Electric.

10.2.1 Problem: Drive Does Not Start From Terminal

Block Start or Run Inputs

Table 10.2 – Problem: Drive Does Not Start From Terminal Block Start or Run Inputs

Possible Cause(s)

Indication

Corrective Action

Drive is faulted

Flashing red
FAULT LED

Clear fault by using one of
the following methods:

Press Stop

Cycle power

Set A100 (Fault Clear) to
1 (Clear Faults)

Cycle digital input if A051/
A052 (Digital Inx Select)
is set to option 7 (Clear
Fault).

Incorrect programming.

P036 (Start Source) is set
to option 0 (Keypad) or
option 5 (RS485 Port).

A051/A052 (Digital Inx
Select) is set to option 5
“Local” and the input is
active.

None

Check parameter settings.

Incorrect input wiring. See
figure 6.2 for wiring
examples.

2-wire control requires
Run Forward, Run
Reverse or Jog input.

3-wire control requires
Start and Stop inputs

Stop input is always
required.

None

Wire inputs correctly and/or
install jumper.