34.4. Analogue output module AN series

Module of analogue outputs


Module accessible in three configurations:

Voltage output AN 0-10V

Current output AN 4-20mA

Current output AN 0-20mA



34.4.1. Technical specification

Work modes

4 - 20mA , 0 - 20mA, 0 - 10V

Resolution 16

bit

Current output resistance

<500

Voltage output resistance

>400

Power supply

24V DC (12 - 30V DC) max 40mA



34.4.2. The way of installing inside PUE 5

These modules are intended to mount inside PUE 5. They need to be
connected to the 10-pin J22 connector. For all configurations of AN, there
is a gland installed on the back wall of the housing. A 3-meter shielded
cables are led out via the gland. Wires should be free from insulation.


Installing procedure:

1. Unplug the terminal from mains;
2. Unscrew and take off the back wall of the housing;
3. Install your module in J22 on the main board;