Tank Location and Installation

Installation

Instructions

ATTENTION

The following is supplied for informational purposes

only.

Tank installation shall only be accomplished by a

qualified LP gas installation person.

State and local codes must be observed at all times.

In absence of state and local codes, follow

ANSI/NFPA58 Standard for Storage and Handling of

Liquefied Petroleum Gases.

Once the proper size of the LP gas supply tank(s) has been

determined, attention must now be given to the most

convenient, yet safe, location of the tanks on the customer’s

property.

Tanks should be placed in a location pleasing to the

customer that does not conflict with state or local

regulations or NFPA 58 (Storage and Handling of Liquefied

Petroleum Gases).

Generally, LP gas tanks should be placed in an accessible

location for filling, supported by concrete of appropriate size

and reinforcement, and located away from vehicular traffic.

Where the tank may be subjected to abrasive action or

physical damage due to vehicular traffic or other causes, it

must be placed not less than two feet below grade, or

otherwise protected against such physical damage.

Regardless of its size, attention must be paid to the tank

distance from building openings, external sources of ignition,

intakes to any outdoor mounted heaters, or mechanical

ventilation systems. Refer to NFPA58 and the following

illustration for the minimum distances that the LP gas tanks

must be placed from the building or other objects.

INLET / EXHAUST FANS

501-2,000

GALLON TANK

CAPACITY

125-500 GALLON

TANK CAPACITY

10' MIN

10' MIN

25' MIN

(SEE NOTE 2)

VENTILATION FANS

NEAREST LINE OF ADJOINING PROPERTY

WHICH MAY BE BUILT UPON

NOTE: 1. REGARDLESS OF SIZE, ALL TANKS FILLED ON SITE MUST BE LOCATED AT LEAST 10 FEET FROM

NEAREST SOURCE OF IGNITION (FANS, HEATERS, ETC.)

2. THIS DISTANCE MAY BE REDUCED TO NO LESS THAN 10' FOR A SINGLE CONTAINER OF 1200 GALLON
CAPACITY OR LESS, PROVIDED THAT THE CONTAINER IS AT LEAST 25' FROM ANY OTHER L.P. GAS
CONTAINER OF MORE THAN 125 GALLON CAPACITY.

3. DISTANCE FROM TANK TO BUILDING FOR TANKS OF 2,001-30,000 GALLON CAPACITY IS 50 FEET.

25' MIN