2.8-1

1

August 1999

Electrical Requirements

Installation

Instructions

ATTENTION

The following is supplied for informational purposes

only.

All electrical wiring shall be accomplished by a

qualified electrician.

Local and state codes must be observed at all times.

In absence of local or state codes, follow

ANSI/NFPA70 National Electrical Code.

Strict attention must be given to the following areas before

connecting the heater to its electrical supply.

A properly installed three-wire electrical supply

consisting of separate hot, neutral, and ground leads

shall be connected to each electrical outlet that

supplies each heater.

Proper voltage must be supplied to each heater.

-- Proper voltage is 115 V.A.C.

+10% (127 volts maximum)

- 15% (98 volts minimum)

-- Under voltage may cause:

*

Low motor speed

*

High limit switch tripping

*

Burner flame cycling on/off

*

Control valve solenoid hums

or does not open.

-- Over voltage may cause:

*

Motor thermal overload tripping

A three-wire cord set (consisting of hot, neutral and

ground leads) of proper wire gauge and desired

length, must be obtained through local sources when

connecting a remote mount thermostat to the heater.