High-Limit Switch Replacement

Servicing

Instructions

12”

Formed Tabs

Spacer

8.7-2

2

August 1999

Specifically relating to the AB200 heater, the high limit is a

capillary and switch mounted to a bracket near the burner.

If switch replacement is necessary you will need to route the

capillary behind the burner, and then across the heat

chamber face, allowing 12 inches of capillary to be in

contact with the heat chamber. The capillary is held in

position by tabs that are formed from the heat chamber.

Insure you have also installed the spacer clips on the

capillary to prevent premature high limit tripping.

ATTENTION

Four spacer clips are required per switch (spacer

part #130-09051).

Install and position the spacers as illustrated.

Do not kink the capillary tube, or pinch it between

the formed tabs and the heat chamber by using

unnecessary force. Capillary damage with

subsequent switch failure will occur.

Capillary R

Routed

Over S

Spacer

High LLimit S

Switch

Dashed LLine

Indicates

Capillary R

Routing

Behind B

Burner

Capillary B

Beneath

Spacer