Servicing instructions – L.B. White Pilot User Manual

Page 74

Advertising
background image

Leak and Gas Pressure Checks

Servicing

Instructions

D. Reading PPressures

1. With the heater operating, the pressure gauges

should read the pressures specified on the dataplate,

or in the specification section of this guide.

2. Do the readings at the inlet and outlet pressure

gauges agree with that specified on the dataplate? If

so, then no further checking or adjustment is

required. Proceed to Section F.

3. If the inlet pressures do not agree with that specified

on the dataplate, then the building system regulator

controlling gas pressure to the heaters requires

adjustment.

4. If the inlet pressures are correct but the burner

manifold pressure does not agree with that specified

on the dataplate, then the gas control valve’s internal

pressure regulator requires adjustment. Proceed to

Section E.

E. Burner M

Manifold PPressure AAdjustment

Refer to the following instructions, after proper inlet pressure

has been established.

1. Light the heater. Once the heater has lit, observe at

the manifold (outlet) pressure gauge. Burner manifold

pressure must be the same pressure as given on the

dataplate.

2. If the manifold pressure does not correspond to the

manifold pressure given on the dataplate, the outlet

pressure must be adjusted at the valve by following

these instructions. (This procedure must be

accomplished with the burner on.)

a. Remove the regulator cap on the control valve to

expose the output pressure adjusting screw.

(Valve shown outside of heater for clarity of viewing.)

b. Using a standard screwdriver, turn the plastic

adjusting screw until the gauge reads proper

manifold pressure. Clockwise increases outlet

pressure. Counterclockwise will decrease

pressure.

c. Reinstall regulator cap on valve.

NOTE:

Procedures for adjusting outlet pressure on control valves

used on earlier models are the same. However, the internal

regulator on the valve is at a slightly different location.

3. Close the fuel valves and disconnect the electrical

supply to the heater.

4. Remove gauges and adapters and reinstall the

pressure tap plugs, tightening both securely.

5. Open the fuel supply valves and reconnect heater to

electrical supply. Test heater for proper operation.

F. Completion

1. Once inlet and burner manifold pressures have been

confirmed and/or properly set, close the fuel supply

valve to the heater and allow the heater to burn off any

as remaining in the gas supply line.

2. Disconnect the heater from its electrical supply.

3. Remove the gauges and connecting hoses.

4. Reinstall the pressure tap plugs and tighten securely.

Check for gas leaks to insure the tap screws have

seated properly.

8.9-3

3

August 1999

Regulator
Cap

Advertising