Testing and adjustment – Garland G SERIES GAS RESTAURANT RANGES User Manual

Page 9

Advertising
background image

Part # 4523104 Rev 3 (03/04/10)

Page 9

TESTING AND ADJUSTMENT

Testing

All fittings and pipe connections must be tested for

leaks . Use approved gas leak detectors, soap solution or

equivalent, checking over and around all the fittings and

pipe connections . DO NOT USE A FLAME! Accessibility to

all gas lines and fittings require that valve panel(s) lower

front panel(s), and/or oven rack(s) be removed . It may be

necessary to remove, or at least raise and securely prop

griddle(s), hot top(s), and/or top grate(s) . All parts removed,

(including fasteners), should be stored safely for re-

installation .

1 . Be sure that all valves and thermostats are in the “OFF”

position .

2 . Turn on the main gas supply valve . Light all top section

pilots .

3 . Leak test all valves and fittings as described at the

beginning of this section . Correct any leaks as required

and recheck .

4 . Light the oven pilot .

5 . Set the oven thermostat to maximum . Leak test all valves

and fittings as described at the beginning of this section .

Correct any leaks as required and recheck .

6 . Shut off all valves and set thermostat dials to “OFF” or

lowest position . All units are tested and adjusted at the

factory, however, burners and pilots should be checked

upon installation and adjusted if necessary .

CAUTION: Gas will flow to the top section burners even

if top section pilots are not lit, except for thermostat

controlled griddles . Gas will not be interrupted . It is the

responsibility of the operator to confirm the proper

ignition of each burner as it is turned on . Should ignition

fail to occur 4 seconds after turning a burner on, turn the

burner off, wait 5 minutes, and try again .

Advertising