Commissioning

Initial switch-on

28

Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.4

Initial switch-on

Establishing communication

• To establish a communication, the Inverter Drive must be supplied with mains voltage.
• For AS-i communication, the Communication Unit has to be supplied with voltage. If this is not

the case, the error message "CE04: MCI communication error" (error no. 01.0127.00002) is

output.

• The

Voltage supply

( 23)

via the AS-i bus cable serves to maintain the AS-i communication in

case of a main supply failure.

• During mains connection, all parameters (codes) are read.
• Addressing can be carried out automatically via the master, an external addressing unit or

manually via codes in the »Engineer«.

Addressing the AS-i slaves

( 26)