1 ctt2: read parameter value, Ctt2: read parameter value, Parameter data transfer – Lenze E84DGFCA User Manual

Page 44

Advertising
background image

Parameter data transfer

CTT2: Read parameter value

44

Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.1

CTT2: Read parameter value

• Acyclic read request from the master to the slave:

• Response from slave to master is OK:

• Response from slave to master has failed:

Byte

Contents / value

0

CTT2: Code

• Index 0x12 (18): Acyclic read request

1

CTT2: Index

• Index 0x10 (16): Read parameter value

2

CTT2: Number of bytes

• Value depends on the master.

Byte

Contents / value

0

CTT2: Code

• Index 0x52 (82): Acyclic read request is OK.

1

Data type / number of bytes
Bit 7 = 0

Octet string (text)

• Bits 0 ... 6 = Number of string characters

Bit 7 = 1

Number (4 data bytes):

• Bits 0 ... 2 = Number of valid bytes

(1 = 1 byte, 2 = 2 bytes, 3 = 3 bytes, 4 = 4 bytes)

2

1st character of the character string or data byte 1 (MSB)

3

2nd character of the string or data byte 2

4

3rd character of the string or data byte 3

5

4th character of the string or data byte 4 (LSB)

6

5th character of the string

...

...

n

n-th character of the string

Byte

Contents / value

0

CTT2: Code

• Index 0x92 (146): Acyclic read request is not OK.

1

CTT2: Standard error code

CTT2: Standard error codes ( 51)

2

Error code (MSB)

3

Error code

4

Error code

5

Error code (LSB)

CTT2: Acyclic device error codes ( 52)