Parameter reference

Parameters relevant for AS-i communication

63

Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13207

C13208

C13210

Parameter | Name:

C13207 | Response in case of communication fault

Data type: UNSIGNED_8

Index: 11368 = 0x2C68

The response set here is triggered if the AS-i node does not receive a message from the master within the

monitoring time (

C13208

) or detects that it has exited the DATA_EXCHANGE status.

A change in the monitoring response becomes immediately effective.
Selection list

(Lenze setting printed in bold)

0 No response
1 Fault
4 Warning Locked

Subcodes

Lenze setting

Info

C13207/1

1

Slave 1 communication timeout

C13207/2

1

Slave 1 communication timeout - CTT2 extended cyclic

C13207/3

1

Slave 2 communication timeout

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13208 | AS-i monitoring times

Data type: UNSIGNED_16

Index: 11367 = 0x2C67

If the DATA_EXCHANGE status is exited, the response parameterised in

C13207/1...3

is carried out when the time

set here for the data exchange has elapsed.

• The value "65535" is used to deactivate the monitoring.

• A change in the monitoring is immediately effective.

Setting range

(min. value | unit | max. value)

0

ms

65535

Subcodes

Lenze setting

Info

C13208/1

3000 ms

Slave 1 monitoring time

C13208/2

3000 ms

Slave 1 monitoring time - CTT2 extended cyclic

C13208/3

3000 ms

Slave 2 monitoring time

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13210 | AS-i Bus transaction counter

Data type: UNSIGNED_16

Index: 11365 = 0x2C65

Display of AS-i transactions
Display range

(min. value | unit | max. value)

0

65535

Subcodes

Info

C13210/1

Slave 1 - Data cycles

C13210/2

Slave 1 - Parameter cycles

C13210/3

Slave 1 - CTT2 extended cyclic cycles

C13210/4

Slave 1 - CTT2 acyclic access cycles

C13210/5

Slave 2 - Data cycles

C13210/6

Slave 2 - Parameter cycles

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT