Parameter reference

Communication-relevant parameters of the operating system

60

Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12

Parameter reference

This chapter supplements the parameter list and the table of attributes in the software manual and

in the »Engineer« online help for the Inverter Drive 8400 motec by the parameters for AS-i

communication.

12.1

Communication-relevant parameters of the operating system

This chapter lists the communication-relevant parameters of the 8400 motec operating system in

numerically ascending order.

C01501

C01503

Software manual/»Engineer« online help "Inverter Drive 8400 motec"
Here you will find general information on parameters.

Parameter | Name:

C01501 | Response in case of communication fault with MCI

Data type: UNSIGNED_8

Index: 23074 = 0x5A22

Setting the response to a communication fault or an incompatible communication unit
Selection list

0 No response
1 Fault
4 Warning Locked

Subcodes

Lenze setting

Info

C01501/1

1: No response

Resp. to MCI fault 1

• Response to a communication fault.

C01501/2

1: No response

Resp. to MCI fault 2

• Response to an incompatible communication unit.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01503 | MCI timeout

Data type: UNSIGNED_16

Index: 23072 = 0x5A20

Setting range

(min. value | unit | max. value)

0

ms

1000

Subcodes

Lenze setting

Info

C01503/1

200 ms

MCI timeout

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1