Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013

35

Data transfer

Data transmission slave 1 (AS-i profile 7.A.5)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Extended process image for slave 1
Extended process image 1 - PR0 = 0

Extended process image 2 - PR0 = 1

Position

Signal / I/O mapping

Master Slave (2 x 16 bits/word)
Word 1

MCI_wIn2/CAN1_wIn2

Word 2

MCI_wIn5/CAN2_wIn1

Slave Master (2 x 16 bits/word)
Word 1

MCI_wOut2/CAN1_wOut2

Word 2

MCI_wOut5/CAN2_wOut1

Position

Signal / I/O mapping

Description

Master Slave (2 x 16 bits/word)
Word 1

MCI_wIn2/CAN1_wIn2

Word 2

MCI_wIn5/CAN2_wIn1

Slave Master (2 x 16 bits/word)
Word 1

MCI_wOut2/CAN1_wOut2

Word 2:

Bits 0 ... 9

0 ... 10 V

(Voltage at analog input)

10 V = 1000

Word 2:

Bit 10

DI3

0: Active

1: Not active

Word 2:

Bit 11

DI4

Word 2:

Bit 12

DI5

Word 2:

Bit 13

Reserved

Word 2:

Bit 14

I/O status information

0: Invalid data in word 1, word 2

1: Valid data in word 1, word 2

Word 2:

Bit 15

Status of the drive (Drive Unit)

0: Drive (Drive Unit) is "offline"

1: Drive (Drive Unit) is "online"