2 possible causes and remedies, 0x01bc3100, 0x01bc5531 – Lenze E84DGFCA User Manual

Page 56: 0x01bc5532, Error messages

Advertising
background image

Error messages

Possible causes and remedies

56

Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.2

Possible causes and remedies

In this chapter, all AS-i error messages are listed in the numerical order of the error numbers.

Possible causes and remedies as well as responses to the error messages are described in detail.

Drive offline [0x01bc3100]

Drive parameter access failure - channel 1 [0x01bc5531]

Drive parameter access failure - channel 2 [0x01bc5532]

Response (Lenze setting printed in bold)

Setting:

C01501/2

/

C01503

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• The communication Unit is supplied with external

voltage, but the Inverter Drive 8400 motec is not

supplied with voltage.

• The Communication Unit is not connected correctly

to the Drive Unit.

• Switch the voltage supply of the Inverter Drive 8400

motec off and on again.

• Check wiring and terminals.

• Check the internal plug connection between

Communication Unit and Drive Unit.

For this purpose, the Inverter Drive 8400 motec must

be unscrewed. Please observe the information

provided in the mounting instructions for the

Communication Unit and Drive Unit!

• If this error continues to occur, please contact the

Lenze service. (it might be necessary to replace the

Communication Unit.)

Response (Lenze setting printed in bold)

Setting:

C01501/2

/

C01503

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• AS-i voltage supply interrupted.

• Connection between the Communication Unit and

the Drive Unit defective.

• Check wiring and terminals.

• Switch the voltage supply of the Inverter Drive 8400

motec off and on again.

• If this error continues to occur, please contact the

Lenze service. (it might be necessary to replace the

Communication Unit.)

Response (Lenze setting printed in bold)

Setting:

C01501/2

/

C01503

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• AS-i voltage supply interrupted.

• Connection between the Communication Unit and

the Drive Unit defective.

• Check wiring and terminals.

• Switch the voltage supply of the Inverter Drive 8400

motec off and on again.

• If this error continues to occur, please contact the

Lenze service. (it might be necessary to replace the

Communication Unit.)