2 parameters relevant for as-i communication, C13200 | active address, C13202 | slave address epm value – Lenze E84DGFCA User Manual

Page 61: C13200/x, C13202/x, C13202/1, C13202/2, Parameters relevant for as-i communication, Parameter reference

Advertising
background image

Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013

61

Parameter reference

Parameters relevant for AS-i communication

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.2

Parameters relevant for AS-i communication

This chapter lists the AS-i parameters of the communication unit in numerically ascending order.

C13200

C13202

Parameter | Name:

C13200 | Active address

Data type: UNSIGNED_8

Index: 11375 = 0x2C6F

Display of the active address of the inverter in the AS-i network

Addressing the AS-i slaves ( 26)

Selection list

(read only)

Info

0 Slave 0(A)

... ...

31 Slave 31(A)
32 Slave 0(B) - invalid
33 Slave 1(B)

... ...

63 Slave 31(B)
64 Slave not active

An error message is generated when a slave is

deactivated.

Subcodes

Info

C13200/1

Slave 1: Active address

C13200/2

Slave 2: Active address

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13202 | Slave address EPM value

Data type: UNSIGNED_8

Index: 11373 = 0x2C6D

Selection of the address of the inverter in the AS-i network

Addressing the AS-i slaves ( 26)

Selection list

(Lenze setting printed in bold)

0 Slave 0(A)

... ...

31 Slave 31(A)
32 Slave 0(B) - invalid
33 Slave 1(B)

... ...

63 Slave 31(B)
64 Slave not active

An error message is generated when a slave is

deactivated.

Subcodes

Lenze setting

Info

C13202/1

0

Slave 1: Address EPM value

C13202/2

0

Slave 2: Address EPM value

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT