Module parameter access failure [0x01bc6102]

Slave 1 data exchange timeout [0x01bc813a]

Slave 1 CTT2 extended cyclic timeout [0x01bc813b]

Slave 2 data exchange timeout [0x01bc813c]

Response (Lenze setting printed in bold)

Setting:

C01501/1

/

C01503

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• AS-i voltage supply interrupted.

• Connection between the Communication Unit and

the Drive Unit defective.

• Check wiring and terminals.

• Switch the voltage supply of the AS-i network off and

on again.

• If this error continues to occur, please contact the

Lenze service. (it might be necessary to replace the

Communication Unit.)

Response (Lenze setting printed in bold)

Setting:

C13207/1

/

C13208/1

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• AS-i communication / voltage supply interrupted.

• The monitoring time is too low.

• Check wiring and terminals.

• Switch the voltage supply of the AS-i network off and

on again.

• Check and raise the monitoring time.

• Check and adjust the AS-i settings of the master.

• Check and adjust the AS-i profile settings of the

master and the slaves.

Response (Lenze setting printed in bold)

Setting:

C13207/2

/

C13208/2

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• AS-i communication / voltage supply interrupted.

• The monitoring time is too low.

• Check wiring and terminals.

• Switch the voltage supply of the AS-i network off and

on again.

• Check and raise the monitoring time.

• Check and adjust the CTT2 settings of the master.

• Check and adjust the AS-i profile settings of the

master and the slaves.

Response (Lenze setting printed in bold)

Setting:

C13207/3

/

C13208/3

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• AS-i communication / voltage supply interrupted.

• The monitoring time is too low.

• Check wiring and terminals.

• Switch the voltage supply of the AS-i network off and

on again.

• Check and raise the monitoring time.

• Check and adjust the AS-i settings of the master.

• Check and adjust the AS-i profile settings of the

master and the slaves.