Parameter setting

6-1

L

BA2102EN

6

Parameter setting

The parameter setting for the 2102 fieldbus module comprises:

Controller parameters which can also be set with the operating units 8201BB or 9371BB.

2102 parameters, which can only be accessed via the 2102 fieldbus module.

Only the controller parameters are permanently saved in the corresponding controller.

Only the parameters important for the serial communication are listed in the following and in the
code table (see chapter 8.2). For further information about the parameter setting see the Manual or
the Operating Instructions of the controllers.

6.1

Parameter sets

6.1.1

82XX parameter sets

The 82XX controller is equipped with 2 directly addressable parameter sets. They are addressed by
means of a code-digit offset:

Offset 0 addresses parameter set 1 with the codes C0000 to C1999.

Offset 2000 addresses parameter set 2 with the codes C2000 to C3999.

If a parameter is only available once (see Operating Instructions 82XX), use the code-digit offset 0.

Example:
C011 = maximum field frequency
C011 in parameter set 1: code number = 11
C011 in parameter set 2: code number = 2011

Changes of the parameters are automatically saved in the controller (see Operating Instructions
82XX).Process data, for instance control words or setpoints are excluded.

6.1.2

Parameter sets for 8200 vector

The 8200 vector controllers are equipped with 4 directly addressable parameter sets. They are
addressed by means of a code-digit offset:

Offset 0 addresses parameter set 1 with the codes C0000 to C1999.

Offset 2000 addresses parameter set 2 with the codes C2000 to C3999.

Offset 4000 addresses parameter set 1 with the codes C4000 to C5999.

Offset 6000 addresses parameter set 2 with the codes C6000 to C7999.

If a parameter is only available once (see 8200 vector Operating Instructions), use code offset 0.

Example:
C011 = maximum field frequency
C011 in parameter set 1: code number = 11
C011 in parameter set 2: code number = 2011
C011 in parameter set 3; code number = 4011
C011 in parameter set 4; code number = 6011

Changes of the parameters are automatically saved in the controller (see Operating Instructions
8200 vector). Process data, for instance control words or setpoints are excluded.

6.1.3

Parameter sets for 93XX

The 93XX controllers are equipped with 4 parameter sets for non-volatile storage. Another
parameter set is in the user memory of the controller. This is the current parameter set. Only the
current parameter set can be directly addressed. Codes: See Operating Instructions or Manual
93XX. Changes of the current parameter set will be lost after switching off the controller. Code C0003
is for saving the current parameter set. After switching on the controller, parameter set 1 is
automatically loaded into the current parameter set.