Appendix, Show/hide bookmarks – Lenze EMF2102IB User Manual

Page 36

Advertising
background image

Appendix

8-4

L

_^ONMObk

Code

Note

Name

C0068

*

Operating status for:

Bit

82XX

8200 vector

93XX

C0068

Operating status for:

82XX

8200 vector

93XX

0 - 3

Operating fault (TRIP)
The 10th digit of the LECOM fault number (see C0161 to C0164) is displayed.

Example: TRIP OH = 5 (LECOM no. = 50)

93XX

(P2102)

4 - 7

Last communication error
0

=

No fault

1

=

Check sum error

2

=

Protocol frame error

3

=

Reserved

4

=

Invalid code number

5

=

Invalid variable

6

=

No access permission

7

=

Telegram processing interrupted by a new telegram

15

=

General fault

8

Ctrl. enable
0 = no controller enable

1

=

Controller enable

9

Qmin (f

d

≤ f

dQmin

)

0

=

Qmin not active

1

=

Qmin active

FREE; fig C0150.Bit 5
Default setting: Qmin (f

d

≤ f

dQmin

)

0

=

Qmin not active

1

=

Qmin active

10

Direction of rotation
0

=

CW rotation

1

=

CCW rotation

Reserved

11

IMP (pulse inhibit)
0 = Pulses to power stages

inhibited

1 = Pulses for power stages
enabled

FREE; display of C0150 bit 1
Default setting: IMP (Pulse inhibit)

0 = Pulses to power stages inhibited

1 = Pulses for power stages enabled

12

QSP (quick stop)
0

=

QSP not active

1

=

QSP active

Reserved

13

I

max

(current limit reached)

0

=

Current limit not

reached

1

=

Current limit reached

FREE; display of C0150 bit 2
Default setting: I

max

(Current limit reached)

0

=

Current limit not reached

1

=

Current limit reached

14

f

d

= f

dset

(Act. frequency =

Frequency setpoint)

0

=

f

d

<> f

dset

1

=

f

d

= f

dset

FREE; display of C0150 bit 4
RFG on = RFG off

(Ramp-function generator input = ramp-function generator output)

0

=

HLG on <> HLG off

1

=

RFG on = RFG off

15

TRIP (fault)
0

=

No error

1

=

Fault occurred

LECOM format: VH

C0125

*

LECOM baud rate

(P82XX)
(P93XX)

0

9600

Baud (Factory setting)

1

4800

Baud

2

2400

Baud

3

1200

Baud

4

19200 Baud

Transmission rate for LECOM-A/B/LI in bit/s (= baud).

LECOM format: VD

C0127

Selection Setpoint
selection

(P821X, P822X, P824X)
(P2102)

0

Absolute setpoint selection

1

Normalized setpoint selection

LECOM format: VD

Show/Hide Bookmarks

Advertising