Parameter setting

6-2

L

BA2102EN

6.2

Meaning of individual parameters

6.2.1

Operating mode

82XX / 8200 vector controllers

Code C0001 (operating mode) determines the source (terminal, keypad, LECOM) which writes the
frequency setpoint (C0046) and the control word (C0135).

Independently of the selected operating mode C0001, the controller can be inhibited under C0040
via LECOM.

Tip!

Please note that the operating mode C0001 is available in both parameter sets. Thus, C0001 must
be set identically in both parameter sets.
For LECOM control (C0001 = 3), the operating mode in parameter set 1 applies 1. For terminal
control (C0001 <> 3), the operating mode in parameter set 1 and parameter set 2 applies.

93XX controllers

The 93XX controller does not offer an operating mode which can be changed by only one code - as
available in the 82XX controller. The 93XX controller is operated via the so-called ” Control codes” .
If, for instance, the speed setpoint is to be changed via LECOM, it is necessary to define a control
code as source for the speed setpoint input of the speed controller. Select the configuration of the
control code so that you can enter the speed setpoint via the 2102 fieldbus module. For further
information please refer to the Manual 93XX.