3 technical data, 1 features of the 2102 fieldbus module, 2 general data and application conditions – Lenze EMF2102IB User Manual

Page 9: Technical data, 3technical data

Advertising
background image

Technical data

3-1

L

_^ONMObk

3

Technical data

3.1

Features of the 2102 fieldbus module

The 2102 fieldbus module has the following features:

Different communication media:
– RS232 (LECOM-A)
– RS485 (LECOM-B)
– Optical fibre (LECOM-LI)

LECOM protocol V2.0

The baud rate can be set to 1200, 2400, 4800, 9600 or 19200 baud (bit/s).

Parameter setting via controller code numbers

3 Diagnostic LEDs

Electrical isolation between control stage and power stage

Electrical isolation of the I/O terminals of 821X, 8200 vector, 822X and 93XX

Easy installation

3.2

General data and application conditions

Field

Values

Communication media

RS232 (LECOM-A): copper conductor
RS485 (LECOM-B): copper conductor

(LECOM-LI): optical fibre

Protocol

LECOM-A/B V2.0

Character
Format

7 bit ASCII
1 Stop bit

1 Start bit

1 Parity bit (even)

Baud rate [bits/s]

1200, 2400, 4800, 9600, 19200

Ambient temperature

During operation:

0

to

+50

°C

Transport:

–25

to

+70

°C

Storage:

–25

to

+55

°C

Permissible moisture

Class 3K3 to EN 50178 (without condensation, average relative humidity 85%)

24-V-DC-
Voltage supply

820X / 8200 vector (observe chapter 4.3):

only external supply

821X / 822X / 8200 vector (observe chapter 4.3) / 93XX:

internal or external supply

Show/Hide Bookmarks

Advertising