Assignment of the 9-pin Sub-D plug connector

5.2.2.2

Specification of the CAN bus cable

We recommend the use of CAN cables according to ISO 11898-2:

View

Pin

Assignment

1

-

2

CAN-LOW

3

CAN-GND

4

-

5

-

6

-

7

CAN-HIGH

8

-

9

-

1

6

5

9

CAN cable according to ISO 11898-2
Cable type

Twisted in pairs with shield

Impedance

120  (95 ... 140 )

Cable resistance/cross-section

Cable length  300 m:

Cable length 301 ... 1000 m:

70 m/m / 0.25 ... 0.34 mm

2

(AWG22)

40 m/m / 0.5 mm

2

(AWG20)

Signal propagation delay

5 ns/m