2 segment cable length, Segment cable length, 5installation – Lenze EMF2180IB User Manual

Page 24

Advertising
background image

5

Installation

5.2

Electrical installation

24

Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.3.2

Segment cable length

The segment cable length is determined by the cable cross-section used and by the number of

nodes. Repeaters divide the total cable length into segments. If no repeaters are used, the segment

cable length is identical to the total cable length.

Example: Selection help

Max. number of

nodes per segment

Cable cross-section (can be interpolated)

0.25 mm

2

(AWG 24)

0.50 mm

2

(AWG 21)

0.75 mm

2

(AWG 19)

1.00 mm

2

(AWG 18)

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

100

150 m

270 m

410 m

600 m

Given
Total cable length to be

implemented

200 m

Number of nodes

63

Results
Max. possible baud rate

250 kbit/s

(derived from the table

Total cable length ( 23)

)

Required cable cross-section

(interpolated)

0.30 mm

2

(AWG23)

(derived from the table

Segment cable length ( 24)

)

Cable cross-section of standard CAN

cable

0.34 mm

2

(AWG22)

Specification of the CAN bus cable ( 22)