C0360

C0361

C1200

Address ranges

Parameter | Name:

C0360 | CAN frame counter

Data type: INTEGER_32

Index: 24215 = 0x5E97

All CAN frames of the CAN node that have been transmitted and received are counted.

The counters have 32 bits, i. e. when a value of 4294967295 is exceeded, the counting process starts again at 0.
Display range

(min. value | unit | max. value)

-2147483647

2147483647

Subcodes

Info

C0360/1

Number of frames transmitted

C0360/2

Number of frames received

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C0361 | CAN bus load

Data type: INTEGER_32

Index: 24214 = 0x5E96

Using this code the percentage total bus load can be determined. Erroneous messages are not taken into account

here.

Note:

• The bus load for all devices involved should not exceed 80 %.

• If other devices, e. g. decentralised inputs and outputs are connected, these messages are also to be taken into

account.

Display range

(min. value | unit | max. value)

0

%

100

Read access  Write access  CINH  PLC-STOP  No transfer

Parameter | Name:

C1200 | Parameter data channel

Data type: INTEGER_32

Index: 23375 = 0x5B4F

This code indicates which of the two parameter data channels is used to communicate with other nodes. The

unused parameter data channels can be switched off, if required.

All Lenze inverters are provided with two parameter data channels featuring different addresses. The address of

parameter data channel 2 is calculated as follows:

Address of parameter data channel 2 = address of parameter data channel 1 + offset 64

Note:

The selection 0 means that the bus is operating in compliance with CANopen and there is no limitation on the

address space.

In this case, the parameter data channel SDO2 is inactive.
Selection list

(Lenze setting printed in bold)

0 CANopen
1 1
2 2

Read access  Write access  CINH  PLC STOP  No transfer

Selection

Accessible address range

Active parameter data channels

0

1...127

SDO 1

1

1 ... 63

SDO 1 / SDO 2

2

65 ... 127

SDO 1 / SDO 2