Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17

53

9

Parameter reference

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9

Parameter reference

This chapter lists all parameters of the communication module in numerically ascending order.

C0002

C0093

C0099

Parameter | Name:

C0002 | Load default setting

Data type: INTEGER_32

Index: 24573 = 0x5FFD

C0002 shows the status of the device command executed last.

C0150

can be used to enquire the current status of

the device control.
Selection list

(Lenze setting printed in bold)

Info

0 Load Def.

Load Lenze standard setting

• Only possible with controller inhibit and stopped user

program.

1 Load PS

Load parameter set

• The parameter set stored in the memory module is

loaded.

• Only possible with controller inhibit and stopped user

program.

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C0093 | Device type

Data type: INTEGER_32

Index: 24482 = 0x5FA2

The display for the EMF2180IB communication module is "2180 0000".
Display range

(min. value | unit | max. value)

-214748

214748

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10000

Parameter | Name:

C0099 | Software version

Data type: INTEGER_32

Index: 24476 = 0x5F9C

Display "x.y"

(x: major version, y: index)
Display range

(min. value | unit | max. value)

0.0

100.0

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10000