3 bus cable length (can), 1 total cable length, Bus cable length (can) – Lenze EMF2180IB User Manual
Page 23: Total cable length, 5installation
![background image](/manuals/565920/23/background.png)
Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17
23
5
Installation
5.2
Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.3
Bus cable length (CAN)
5.2.3.1
Total cable length
The baud rate also determines the total cable length.
Note!
• It is absolutely necessary to comply with the permissible cable lengths.
• If the total cable lengths of the CAN nodes differ for the same baud rate, the smaller
value must be used to determine the max. cable length.
• Observe the reduction of the total cable length due to the signal delay of the
repeater.
Baud rate [kbps]
Max. bus length [m]
10
8075
20
4012
50
1575
125
600
250
275
500
112
800
38
1000
12