C0350, Can no, C0351 – Lenze EMF2180IB User Manual

Page 55: 9parameter reference

Advertising
background image

Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17

55

9

Parameter reference

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C0350

C0351

Parameter | Name:

C0350 | CAN node address

Data type: INTEGER_32

Index: 24225 = 0x5EA1

The node address can be set via the CAN bus using the code C0350.

If zero is used as address, the communication module does not have a node address of its own. It can then not be

addressed from the CAN bus (no parameter setting, node guarding, etc.), but only serves as a dial-in option for rea-

ding parameters via the CAN bus.

If the communication module is to have an address, after determination of the baud rate, check whether this

address is still free. Then an attempt is made to read the implemented CANopen object -1000. If this address is

already assigned to another node, another free address is selected automatically.

Note:

Node addresses in the range of 64 ... 127 can only be assigned if code

C1200

is set to the value "0" (CANopen

conformity)

Changes that are made to the settings will be accepted after ...

• reconnection to the mains;

• a "Reset node" or "Reset communication" via the bus system;

• a "Reset node" via code

C0358

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

127 63

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C0351 | CAN baud rate

Data type: INTEGER_32

Index: 24224 = 0x5EA0

The baud rate over the CAN bus can be set using this code.

Prior to accessing the CAN bus, the baud rate used is determined by the communication module and is compared

with the baud rate configured.

If there is a difference between the two values, the baud rate determined is used. Code

C1209

can be used to read

out the baud rate detected by the communication module.

If there is no data exchange on the CAN bus, the baud rate cannot be determined. The subsequent response of the

communication module depends on the selection configured in code

C0351

:

Selection 0 ... 5

After a time-out that can be configured using code

C1215

, the CAN bus is accessed with the baud rate configured.

Selection 16 (automatic detection of the baud rate)

The communication module is not accessed by the bus until a baud rate has been detected.

Changes that are made to the settings will be accepted after ...

• reconnection to the mains;

• a "Reset node" command via the bus system;

• a "Reset node" via code

C0358

.

Selection list

(Lenze setting printed in bold)

0 500 kbit/s
1 250 kbit/s
2 125 kbit/s
3 50 kbit/s
4 1000 kbps
5 20 kbit/s

16 Autom. baud rate detection

Read access  Write access  CINH  PLC STOP  No transfer