LED signalling in compliance with DR303-3

Connection status to the CAN bus with the following signalling:

LEDs

Description

off

Connection to the master is available.

Green

CANopen status ("Z")

Red

CANopen error ("F")

Status display (LED)

Explanation

Constantly red

F: Bus-off

Flicker

Automatic baud rate detection is active.

Blinking green every 0.2 s

Z: Pre-operational, F: No errors

Blinking green every 0.2 s

1 x red blinking, 1 s OFF

Z: Pre-operational, F: Warning limit reached

Green blinking every 0.2 s

2 x red blinking, 1 s OFF

Z: Pre-operational, F: Node guarding event

Constantly green

Z: Operational, F: No errors

Constantly green

1 x red blinking, 1 s OFF

Z: Operational, error: Warning limit reached

Constantly green

2 x red blinking, 1 s OFF

Z: Operational, F: Node guarding event

Constantly green

3 x red blinking, 1 s off

Z: Operational, F: Sync message error

Green blinking every second

Z: Stopped, F: No errors

Green blinking every second

1 x red blinking, 1 s OFF

Z: Stopped, F: Warning limit reached

Green blinking every second

2 x red blinking, 1 s OFF

Z: Stopped, F: Node guarding event