9parameter reference – Lenze EMF2180IB User Manual

Page 57

Advertising
background image

Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17

57

9

Parameter reference

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C0359

Parameter | Name:

C0359 | CAN bus status

Data type: INTEGER_32

Index: 24216 = 0x5E98

This code displays the current operating status of the CAN controller. Here, the following states are distinguished:

Selection 0: "Operational"

In this state the bus system is fully functional.

Selection 1: "Pre-operational"

In this state only parameter data (codes) can be transferred via the bus system. It is not possible to exchange process

data. To change to the "Operational" state, a network management frame must be output on the bus.

A state change from "Pre-operational" to "Operational" can be made with the following actions:

• A drive is defined as master using the inverter code C0352. During mains connection, an automatic state change

for the whole drive system is performed after the boot-up time defined in C0356/1

• "Reset node" via code

C0358

(precondition: C0352 = 1).

• With the "Reset node" binary input signal which can, for instance, be set via a terminal if inverter code C0364 is

configured accordingly (precondition: C0352 = 1).

• A network management message from a CAN master.

Selection 2: "Warning"

Incorrect frames have been received if the state is "Warning". The CAN node is now only involved in a passive way;

no more data are sent from the inverter.

The reason for this situation can be:

• A missing bus terminator

• Inadequate shielding

• Potential differences at the ground connection for the control electronics

• An excessively high bus load

• CAN node is not connected to the bus

Selection 3: "Bus Off"

The frequency of the erroneous frames has caused the CAN node to decouple from the bus. A change-over to "Pre-

Operational" can be effected by ...

• a "TRIP reset";

• a "Reset node";

• reconnection to the mains.

Selection 4: "Stopped"

Only NMT frames can be received.

The state can be changed to "Pre-operational" by ...

• a "Reset node" via code

C0358

;

• a "Reset node" via the bus system;

• reconnection to the mains.

Selection list

(read only)

0 Operational
1 Preoperational
2 Warning
3 Bus Off
4 Stopped

Read access  Write access  CINH  PLC-STOP  No transfer