C1220, C1220/0, 9parameter reference – Lenze EMF2180IB User Manual

Page 63

Advertising
background image

Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17

63

9

Parameter reference

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C1220

C1224

Parameter | Name:

C1220 | CAN device monitoring

Data type: UNSIGNED_8

Index: 23355 = 0x5B3B

This code serves to ...

• activate the CAN device monitoring function (subcode 0);

• detect interrupted CAN communication for each node and record it in a bit mask (subcodes 1 ... 4) when the CAN

device monitoring function is activated.

Recording of interrupted nodes

Subcodes 1 ... 4 contain a bit mask in which each node (a maximum of 127) with interrupted bus communication or

with an inexistent physical presence is recorded with the value "1".

The status bit immediately adopts the value "0" when communication of the node has been re-established.

For testing purposes, the bit mask can be written to by the user. The values written are accepted at the end of the

CAN device monitoring cycle time in each case (

C1217

).

In the »Engineer«, a change-over to the hexadecimal representation is recommended.
Setting range

(min. value | unit | max. value)

0

60000

Subcodes

Lenze setting

Info

C1211/0

0

0: device monitoring not activated

1: device monitoring activated

(Activation can also be carried out via

C1219

or the

gateway configuration web page.)

C1211/1

0

Bits: 31 (MSB) ... 0 (LSB)

C1211/2

0

Bits: 63 (MSB) ... 32 (LSB)

C1211/3

0

Bits: 95 (MSB) ... 64 (LSB)

C1211/4

0

Bits: 127 (MSB) ... 96 (LSB)

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C1224 | Gateway address

Data type: UNSIGNED_32

Index: 23351 = 0x5B37

If the communication module is in another subnetwork than the Engineering PC, the IP address of the

corresponding router must be entered into this code

The data are only accepted when the mains has been switched the next time.
Setting range

(min. value | unit | max. value)

0

255

Subcodes

Lenze setting

Info

C1224/1

0

Gateway Address 1

C1224/2

0

Gateway Address 2

C1224/3

0

Gateway Address 3

C1224/4

0

Gateway Address 4

Read access  Write access  CINH  PLC STOP  No transfer