Digital inputs – Lenze IMSS500+ Simple Servo 500 600 i1000 User Manual

Page 30

Advertising
background image

SimpleServo 500/600/i1000 User Manual Rev 3.4

On TB502:

“OUT_RDY” (TB502-13), “OUT_AUX” (TB502-14).

Functions the same as “READY” and “AUX” have open-collector sinking outputs (sinking only)
referenced to drive logic common. See figure below for the electrical diagram.










Both versions of these outputs (On TB506 and TB502) have the same logic.

“READY” output
Activated when the drive is ready and enabled. It is reset to an inactive state when the drive is
disabled, not operational or any fault is detected.


“AUX” output

Programmable output. Activated when any of the selected conditions are true. These
conditions are software selectable. Use MotionView to select the condition assigned to this
programmable output. Only one condition at a time can be selected for output. Possible
choices are:

• Zero speed

• In speed window

• Current limit

• Run Time Fault

5.2.3 Digital

inputs


“ENABLE+ & ENABLE-” (TB506-17, 18).

Optically isolated input. Compatible with 5 -24V voltage source or open-collector sinking
output. For connection guidelines, refer to the application note in Section 12. See figure
below for electrical diagram.









30