39
Tools Menu Chapter 8
to an oscilloscope or chart recorder). The first screen allows the operator to 
configure the four Class, Instance, or Attributes to be monitored.
Press the Enter key after the CIA data is configured to display the Graph Trigger 
Screen. This screen allows the operator to program a trigger point to stop the 
graph display from updating. The operator can set which trace will be used as the 
trigger as well as the slope, value, and position of trigger. The trigger point can be 
disabled if the operator does not need this feature.
Press the Enter key after the trigger data is configured to display the Graph View 
Screen.
CIA Copy and Paste is 
available for this menu
Class, Instance, 
Attribute to 
graph, Note: 
Traces with the 
class set to zero 
will not be 
graphed.
Trace number 1-4
Max is the CIA’s value that 
will be represented as the 
top of the screen. Min is 
the CIA’s value that will be 
represented as the bottom 
of the screen. (In this 
example, a CIA value of 50 
would be in the middle of 
the screen; any CIA value at 
or above 100 would be 
displayed on the top pixel 
of the screen). Note there 
are only 64 vertical pixels 
Offset is the 
number of pixels 
from the bottom of 
the screen the min 
value for this trace 
will be displayed 
at. The range for 
this field is 0…64, 
with 32 being the 
middle of the 
Rate the CIA will be polled, in 10 mSec 
increments
The value is the trigger 
point; this is the raw value 
obtained by reading the 
CIA for the selected trace.
This could be trace 
1…4
Positive Slope: the 
raw value (obtained 
by reading the CIA 
for the trace) moving 
from below the 
Programmed Value 
to equal or above the 
Programmed Value.
Negative Slope = 
Position value is 0 …128 (128 pixels 
across the screen) 64 = 50%
Position is the location 
on the screen at which 
the trigger point will be 
displayed when the 
trigger condition is 
found.