Devicenet™ error log, Network statistics screen, Devicenet™ error log network statistics screen – Rockwell Automation 193-DNCT DeviceNet Configuration Terminal User Manual User Manual
Page 71
 
Rockwell Automation Publication 193-UM009B-EN-P - February 2013
67
Terminal Choices Menu Chapter 16
DeviceNet™ Error Log
The DeviceNet™ Error Log stores the last five errors the Configuration Terminal 
received when requesting information from a device. If the terminal receives an 
error that is the same as the last error, only the first error will be stored. Errors 
received while in the Who Menu are not entered into the error log. Each error has 
a time stamp associated with it that indicates the number of days, hours, minutes, 
and seconds since the error message was received. The Error Log screen has the 
following format:
Network Statistics Screen
This screen displays some DeviceNet™ network statistics such as baud rate, actual 
bus voltage stats, percentage of bus loading stats, CAN errors per second, and 
total CAN errors. Latching of statistics for some readings begins when the screen 
is entered, and stops when exiting the screen. Statistics can be cleared by exiting 
and re-entering the menu. While displaying this screen, the 193-DNCT will not 
respond to any DeviceNet™ messages directed to it. There will be a short delay 
when exiting this screen before the Terminal starts producing DeviceNet™ 
messages, due to the CAN chip being reset and re-initialized. The Network Stats 
Menu has the following format:
This menu 
supports the 
CIA Copy 
function
Error Buffer 
Number, use the 
Inc/Dec keys to 
scroll through 
each entry in the 
log.
Node Number, 
Class, Instance, 
and Attribute of 
request for which 
an error was 
returned
Requested Service:
Get Single
Set Single
Get All
Set All
Reset
Create
Delete
The Error 
code that 
was returned
Time Stamp:
DDD:HH:MM:SS
D = Days
H = Hours
M= Minutes
S = Second