Programmable user function key setup, Parameter screen, Cia editor screen – Rockwell Automation 193-DNCT DeviceNet Configuration Terminal User Manual User Manual

Page 78: I/o message monitoring screen, Graph view screen, Who menu (reset key only)

Advertising
background image

74

Rockwell Automation Publication 193-UM009B-EN-P - February 2013

Chapter 17 Terminal Setup Menu

Programmable User Function
Key Setup

The 5 user programmable function keys (F1, F2, F3, F4 and Reset) can be
configured to send DeviceNet™ explicit messages when they are pressed. The
Function Key Setup screen is used to associate DeviceNet™ messages to the
various function keys. This screen is accessed by selecting “UserKeys” in the
“Terminal Setup Menu” and pressing the Enter key.

The default operation of these keys is identical to the OutA and OutB start keys,
and the OutA and OutB stop keys on the old Bulletin 193-PCT hand-held
terminal.

· F1

: Default behavior is like that of the green OutA start key on the 193-

PCT. It sets Discrete Output Point instance 1 to the ON state. (CIA:
0x09-0x01-0x03 = 1).

· F2

: Default behavior is like that of the green OutB start key on the 193-

PCT. It sets Discrete Output Point instance 2 to the ON state. (CIA:
0x09-0x02-0x03 = 1).

· F3

: Default behavior is like that of the red OutA stop key on the 193-

PCT. It sets Discrete Output Point instance 1 to the OFF state. (CIA:
0x09-0x01-0x03 = 0).

· F4

: Default behavior is like that of the red OutB stop key on the 193-PCT.

It sets Discrete Output Point instance 2 to the OFF state. (CIA: 0x09-
0x02-0x03 = 0).

· Reset

: Sets Fault Reset to the ON state. (CIA: 0x29-0x01-0x0C = 0).

Each key has the following configuration parameters that can be programmed:
Class, Instance, Attribute, Pressed (Down) Value (ON or OFF) and Mode. The
Mode can be programmed to either Momentary or Maintained operation. The
Maintained Mode acts as follows: when key is pressed, the Press Down Value is
sent; when the key is released there is no operation. The Momentary Mode acts as
follows: when key is pressed, the Press Down Value is sent; when the key is
released, the inverse of the Press Down Value is sent. Since not all screens have an
active explicit message connection, the Function Keys will be active while viewing
only some menu screens. The following is a list of screens on which the User Keys
will be active:

1.

Parameter Screen

2.

CIA Editor Screen

3.

I/O Message Monitoring Screen

4.

Graph View Screen

5.

Who Menu (Reset key only)

Table 17.1 Function Key Default Behavior for E3 and ArmorStart

Function Key

Default E3 Operation

Default ArmorStart Operation

F1

Turns on Output A

Turns on Run Forward

F2

Turns on Output B

Turns on Run Reverse

F3

Turns off Output A

Turns off Run Forward

F4

Turns off Output B

Turns off Run Reverse

Reset

Resets Protection Faults

Resets Protection Faults