Chapter 14 Zone Interlock Protocol (ZIP)
Mapping Consumed ZIP Data
This section explains mapping I/O data for a Zone. Assume that the DeviceNet™ 
Configuration Terminal is currently configuring Node 11 on the Network. Also 
assume Node 5 is on the network, and is producing I/O data. Node 11 will be 
configured to consume the I/O data that Node 5 is producing, which will be 
done by mapping Node 5 I/O data to Zone 1 in the ZIP data table of Node 11.
First, use the Left/Right arrow keys to select the byte in the ZIP data table where 
Node 5 I/O data will be mapped to.
Once the desired byte in the internal ZIP data table is selected, enter a Node 
number using the numeric keys on the keypad of the node whose I/O is to be 
mapped (this example maps Node 5 data to byte 0 of the ZIP data table). Press 
the Enter key after the Node Number has been entered and the following display 
should appear:
Use the Sel key to highlight the various ZIP configuration parameters for this 
zone. The following screen shows the Node field highlighted:
This is Byte 7 of the
ZIP internal data 
table 
The selected byte in the ZIP 
data table is highlighted. In 
this case Byte 0 is selected. 
Use the Right/Left arrow 
keys to select the byte
Node 5 is 
mapped to 
byte 0 of the 
ZIP data table 
These are the 
current ZIP 
configuration 
parameters for 
Zone 1
Zone 1 is now
configured to 
Node 5 
The node: Field allows the node 
number associated with this Zone to 
be changed