Mapping consumed zip data – Rockwell Automation 193-DNCT DeviceNet Configuration Terminal User Manual User Manual

Page 62

Advertising
background image

58

Rockwell Automation Publication 193-UM009B-EN-P - February 2013

Chapter 14 Zone Interlock Protocol (ZIP)

Mapping Consumed ZIP Data

This section explains mapping I/O data for a Zone. Assume that the DeviceNet™
Configuration Terminal is currently configuring Node 11 on the Network. Also
assume Node 5 is on the network, and is producing I/O data. Node 11 will be
configured to consume the I/O data that Node 5 is producing, which will be
done by mapping Node 5 I/O data to Zone 1 in the ZIP data table of Node 11.

First, use the Left/Right arrow keys to select the byte in the ZIP data table where
Node 5 I/O data will be mapped to.

Once the desired byte in the internal ZIP data table is selected, enter a Node
number using the numeric keys on the keypad of the node whose I/O is to be
mapped (this example maps Node 5 data to byte 0 of the ZIP data table). Press
the Enter key after the Node Number has been entered and the following display
should appear:

Use the Sel key to highlight the various ZIP configuration parameters for this
zone. The following screen shows the Node field highlighted:

This is Byte 7 of the

ZIP internal data
table

The selected byte in the ZIP
data table is highlighted. In
this case Byte 0 is selected.
Use the Right/Left arrow
keys to select the byte

Node 5 is
mapped to
byte 0 of the
ZIP data table

These are the
current ZIP
configuration
parameters for
Zone 1

Zone 1 is now

configured to
Node 5

The node: Field allows the node
number associated with this Zone to
be changed