Autodisplay setup, Autodisplay test, Autodisplay setup autodisplay test – Rockwell Automation 193-DNCT DeviceNet Configuration Terminal User Manual User Manual

Page 77

Advertising
background image

Rockwell Automation Publication 193-UM009B-EN-P - February 2013

73

Terminal Setup Menu Chapter 17

intervention at power-up. The following choices appear when AutoDspl is
selected from the Terminal Setup Menu:

AutoDisplay Setup

This screen is used to set up to four Class, Instance Attributes to be auto
displayed. This screen allows a different node address to be entered for each CIA
value configured, thus up to four different nodes can be monitored at the same
time. Setting the node address to 64 for a CIA disables Auto Display for that
value. Use the Sel key to select different fields to edit.

AutoDisplay Test

This function gives the operator an easy way to view and test the AutoDisplay
setup data without powering down the 193-DNCT after setting up each line. If
the CIA data for a line points to the parameter class, the 193-DNCT will display
the scaled value and units (if any) for that line.

CIA Copy and
Paste is
available for this
menu.

Device node
number

Display line
number

(1…4)

This enables or disables the
AutoDisplay on power up. It
can be set on the screen for
any line number but this value
will be the same for all 4 lines.

Class, Instance,
Attribute data

CIA NOT pointing
to a parameter
object

CIA pointing to
a parameter
object

Note: AutoDisplay can
be configured to show
4 lines as shown here
or 1, 2, or 3 lines.

Advertising