Specifications

A-2

ELECTRICAL – CONTROL CIRCUIT (cont.)

Motor Current

Phases

Three-phase or SIngle Phase

Rated Insulation Voltage

660 VAC

Maximum Operational Current

(See Cat. No. Code Explanation)

Operational Frequency

50–60 Hz

Current Wave Shape

Undistorted Sinusodial

ENVIRONMENTAL

Ambient Temperature

Storage

–40

°

C to 85

°

C (–40

°

F to 185

°

F)

Operation (Enclosed)

(Open Enclosure)

–20

°

C to 40

°

C (–4

°

F to 104

°

F)

–20

°

C to 55

°

C (–4

°

F to 131

°

F)

Maximum Altitude

2,000 M (6,562 ft.)

Relative Humidity

5% to 95% (non-condensing)

Cooling Method

Natural Convection

Vibration

1G Operational, 2.5G Non-operational

Shock

15 Operational, 30G Non-operational

Pollution Environment

Degree 2

ENVIRONMENTAL (Cont.)

Terminal Marking

CENELEC EN 50012

Finger Protection

(w/ contactor terminal cover)
(w/o contactor terminal cover)
(CT mounted and NEMA overload)

IP1X (Bul. 193-C1_1, 2, 3)

IP1X (Bul. 193-C1_4, 5)

IP0 (Bul. 193-C1_4, 5)

IP0 (Bul. 592 and Bul. 193-C1_6)

Electrostatic Discharge

8kV Air Discharge

RFI Susceptibility

10V/m

Fast Transient Susceptibility

2kV (AC Lines), 1kV

(Communication Lines)

Impulse Voltage Susceptibility

1kV (Line to line)

2kV (Line to ground)

Radiated Emissions

CISPR11 Group 1 Class A

Conducted Emissions

CISPR11 Group 1 Class A

PROTECTION FEATURES

Overload

Embedded Feature

Trip Class

Selectable (Class 10, 15, 20, or 30)

FLA Setting

Selectable (Up to a 5:1 range)

Phase Loss

Embedded Feature

Ground Fault

Selectable Feature

Jam/Stall

Selectable Feature