Chapter 6 – Serial Communication

6-9

Rung 2:5
Current Unbalance to Rack 3,Word 3
| I:020 I:020 I:020 +MOV–––––––––––––––+ |
+––] [–––]/[–––]/[––––––––––––––––––––––––––––––––––––––––+MOVE +–+
| 07 06 05 |Source I:021| |
| | 0| |
| |Destination O:033| |
| | 0| |
| +––––––––––––––––––+ |

The following section displays the SMP-3 fault status on the panelview.

Rung 2:6
Copy Fault status bits from SMP Status (Rack 2,Word 0, Bits 8–15)
to buffer N31:1 bits 0–7 for comparison purposes.
| +BTD–––––––––––––––+ |
+–––––––––––––––––––––––––––––––––––––––––––––––––––––––––+BIT FIELD DISTRIB +–+
| |Source I:020| |
| | 36| |
| |Source bit 8| |
| |Destination N31:1| |
| | 0| |
| |Destination bit 0| |
| |Length 8| |
| +––––––––––––––––––+ |
Rung 2:7
If any fault bit is set, energize generic fault indicator on Local Rack (Rack 0,Word 1,Bit 7)
| +GRT–––––––––––––––+ O:001 |
+–+GREATER THAN +––––––––––––––––––––––––––––––––––––––––––––––––––––( )––+
| |Source A N31:1| 07 |
| | 0| |
| |Source B 0| |
| | | |
| +––––––––––––––––––+ |