Chapter 8 – Programming

8-4

Mask Programming (Using the HIM in Control Status Mode)

The following procedure describes the programming steps required to mask out the HIM using the control status mode.

Note: Earlier versions of the HIM may not support this mode.

ACTION

DESCRIPTION

HIM DISPLAY

or

ESC

SEL

To Select Mode

SEL

or

ESC ESC

1.

Press any key to go from the Status Display to the Choose Mode menu.

2.

Press the up/down keys to toggle to “Control Status” in the display.

3.

Press Enter to go to the Control Status menu.

4.

Press select to move to the lower line.

5.

Press up/down keys to toggle to either disabled or enabled.

6.

Press Enter. When Disabled is selected the HIM is masked out and can be
disconnected without faulting the SMP-3 overload relay.

7.

Press Escape twice to return to the Status Display.

A=OXX B=OXX

X.X AMPS

Choose Mode
Control Status

Control Logic
Enabled

Control Logic
Disabled

Note:

This procedure can only be used to mask out the HIM. The procedure in the previous example must be used to mask out a second adapter.

ATTENTION: The Mask parameter is a volatile parameter. If power is cycled to the SMP-3 overload relay, the
SMP-3 will power-up with the Mask parameter in its default state ports 1 and 2 (enabled (00000110). The mask must be
re-programmed after a power-up or power loss.