Chapter 3 – Installation and Wiring
3-36
Table 3.I FLC DIP Switch Designations and Minimum Settings
Catalog
er ➊
Current
Range
LC
FLC Switch
Designations
Minimum
Setting
A pere
Number ➊
(FLC
Range)
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
(Amperes)
➋
➌
xxx–C1Dx
(0.7–2.5A)
1.00
0.70
0.40
0.20
0.10
.05
.03
.02
0.70
xxx–C1Fx
(2–10A)
5.0
2.0
1.0
1.0
0.5
0.2
0.2
0.1
2.0
xxx–C1Hx
(8–37A)
15.0
10.0
5.0
4.0
2.0
1.0
0.5
0.2
8.0
xxx–C1Kx
(20–75A)
30
20
10
5
5
2
2
1
20
xxx–C1Lx
(20–90A)
40
25
10
5
5
2
2
1
20
xxx–C1Mx
(40–180A)
75
50
25
10
10
5
3
2
40
xxx–C1Nx
(70–304A)
150
75
40
20
10
5
2
2
70
xxx–C1Px
(100–414A)
200
100
50
25
20
10
5
4
100
xxx–C1Rx
(140–608A)
300
150
80
40
20
10
5
3
140
➊
The X indicates a variable character in the Catalog Number.
➋
If theSMP-3 FLC is set below the minimum allowable setting shown, the SMP-3
overload relay will fault on a Min FLC SET fault, fault code #6.
➌
If the FLC setting is set below the minimum allowable setting, the SMP-3 overload
relay will default to using and reporting the minimum FLC setting shown in Table 3I.