Rockwell Automation 193 193-5.0: Bulletin 913/592 SMP-3 Solid-State Overload Relay User Manual

Page 46

Advertising
background image

Chapter 3 – Installation and Wiring

3-36

Table 3.I FLC DIP Switch Designations and Minimum Settings

Catalog

er

Current

Range

LC

FLC Switch

Designations

Minimum

Setting

A pere

Number

(FLC

Range)

SW1

SW2

SW3

SW4

SW5

SW6

SW7

SW8

(Amperes)

xxx–C1Dx

(0.7–2.5A)

1.00

0.70

0.40

0.20

0.10

.05

.03

.02

0.70

xxx–C1Fx

(2–10A)

5.0

2.0

1.0

1.0

0.5

0.2

0.2

0.1

2.0

xxx–C1Hx

(8–37A)

15.0

10.0

5.0

4.0

2.0

1.0

0.5

0.2

8.0

xxx–C1Kx

(20–75A)

30

20

10

5

5

2

2

1

20

xxx–C1Lx

(20–90A)

40

25

10

5

5

2

2

1

20

xxx–C1Mx

(40–180A)

75

50

25

10

10

5

3

2

40

xxx–C1Nx

(70–304A)

150

75

40

20

10

5

2

2

70

xxx–C1Px

(100–414A)

200

100

50

25

20

10

5

4

100

xxx–C1Rx

(140–608A)

300

150

80

40

20

10

5

3

140

The X indicates a variable character in the Catalog Number.

If theSMP-3 FLC is set below the minimum allowable setting shown, the SMP-3
overload relay will fault on a Min FLC SET fault, fault code #6.

If the FLC setting is set below the minimum allowable setting, the SMP-3 overload
relay will default to using and reporting the minimum FLC setting shown in Table 3I.