Rockwell Automation 193 193-5.0: Bulletin 913/592 SMP-3 Solid-State Overload Relay User Manual
Page 84
![background image](/manuals/578052/84/background.png)
Chapter 6 – Serial Communication
6-14
Rung 2:19
Auto Parameter Selection
Start 30ms Timer to determine when to increment to next parameter
| I:010 +TON–––––––––––––––+ |
+––] [–––––––––––––––––––––––––––––––––––––––––––––––+TIMER ON DELAY +–(EN)–+
| 03 |Timer T4:0| |
| |Time base 0.01+–(DN) |
| |Preset 30| |
| |Accum 0| |
| +––––––––––––––––––+ |
Rung 2:20
Auto Parameter Selection
After 30ms select next parameter
| I:010 T4:0 +ADD–––––––––––––––+ |
+––] [–––] [––––––––––––––––––––––––––––––––––––––––––––––+ADD +–+
| 03 DN |Source A 1| |
| | | |
| |Source B N31:3| |
| | 3| |
| |Destination N31:3| |
| | 3| |
| +––––––––––––––––––+ |
Rung 2:21
Auto Parameter Selection
After 30ms, reset timer
| I:010 T4:0 T4:0 |
+––] [–––] [–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––(RES)–+
| 03 DN |